RIM-Protocol Converter User Guide - Version 1.0
44 www.chatsworth.com
3.7 Set Communication Protocol Options
Set the Modbus, BACnet, or SNMP protocols as described in the following sections.
3.7.1 Modbus/EIA-485 Port Configuration
To configure the Modbus/EIA-485 port, use the top navigation bar to access the Configuration screens. Select the
EIA-485/Modbus/BACnet-MSTP Ports option and configure the fields accordingly.
Figure 3.26 EIA-485/Modbus/BACnet-MSTP Ports Configuration
Table 3.8 EIA-485/Modbus/BACnet-MSTP Ports Configuration Options
Option
Description
Modbus/TCP/UDP Slave
Unit Identifier
Designate the TCP/UDP slave address in the range 1 to 254.
To disable this feature, leave the address set to 0.
Offline Startup Delay
Amount of time, in minutes, that the Protocol Converter waits
before considering any slave device as offline after a power up.
Vue de la page 43